The following operational parameters provide setting of the communication profile:
Menu
Range (OS)*
Default
Serial Timer:
Setting 0,000 allows manual activation of a serial data
transmission at any time. All other settings specify the
cycle time for automatic transmission (provided the Serial
Mode is set to "Printer")
0.000;
0.010…
9..999 sec
0.1 sec
Between two transmission cycles the unit will allow a
pause depending on the baud rate. The minimum cycle
times for timer transmissions are shown in the table.
Baud Rate
Minimum Cycle Time [msec]
600
384
1200
192
2400
96
4800
48
9600
24
19200
12
38400
6
Serial Mode:
Operation according to communication profile (see 5.5.1)
Transmission of string type 1 (see 5.5.2)
Transmission of string type 2 (see 5.5.2)
Serial Register-Code:
Specifies the register code of the data to be transmitted.
The most important register codes are the actual display
value and the serial Set/Reset command code
Register
S-Code
ASCII
Actual display value
101
: 1
Activate SET /RESET
60
6 0
100
...
120
101
*) OS only with DX348
(0)
(1)
(2)