5.2 Mode Speed
This menu defines the operation as speed indicator (RPM), tachometer or frequency meter.
In this operation mode only input A is active or Input A and Input B with 90 ° phase offset for forward /
reverse rotation detection. This menu is only displayed when the appropriate OPERATIONAL MODE in
GENERAL MENU is selected.
DISPLAY VALUE
Desired value, which should be displayed at the setting of BASE FREQUENCY.
1
Smallest value
1000
Default value
99999999
Highest value
BASE FREQUENCY (HZ)
Reference frequency for the desired DISPLAY VALUE.
1
Smallest value
100
Default value
500000
Highest value
DECIMAL POINT
This value defines the position of the decimal point.
0
NO
No decimal point
1
0000000.0
Decimal point at the specified position
2
000000.00
Decimal point at the specified position
3
00000.000
Decimal point at the specified position
4
0000.0000
Decimal point at the specified position
5
000.00000
Decimal point at the specified position
6
00.000000
Decimal point at the specified position
7
0.0000000
Decimal point at the specified position
SAMPLING TIME (S)
The configured value corresponds to the minimum measurement time. The Parameter is used as a filter in case of
irregular frequencies. This parameter directly affects the response time of the unit.
0.005
Shortest Sampling time
0.1
Default value
9.999
Longest Sampling time