Continuation „Mode Process Time“:
WAIT TIME (S)
This parameter defines the period time of the lowest frequency, accordingly the time between two rising signal
edges detecting frequency 0 Hz. Frequencies with a period time higher than the set “WAIT TIME” will be detected as
frequency = 0 Hz.
0.01
Frequency = 0 Hz, for frequencies below 100 Hz
1.00
Default value
99.99
Frequency = 0 Hz, for frequencies below 0,1 Hz
STANDSTILL TIME (S)
This parameter defines the time setting for standstill definition.
A time of xx.xx seconds after detection " frequency = 0 Hz " the unit signals "standstill" and reactivates the start-up-
delays. Stand still detection can be set in PRESELECT MENU.
0.00
Shortest time
99.99
Longest time
AVERAGE FILTER
Selectable average or filter function to avoid measuring fluctuations by unstable frequencies. At setting 1 to 4 a
floating average calculation is preformed. At settings 5 to 8, the device uses an exponential filter. The time
constant T (63%) corresponds to the sampling cycles.
For example: If SAMPLING TIME = 0,1 s and AVERAGE FILTER = Exponential filter, T (63 %) = 2x SAMPLING TIME,
after 0,2 seconds, 63% of the step size are reached
0
No average value will be created
1
2 numbers of floating average cycles
2
4 numbers of floating average cycles
3
8 numbers of floating average cycles
4
16 numbers of floating average cycles
5
Exponential filter, T (63 %) = 2x SAMPLING TIME
6
Exponential filter, T (63 %) = 4x SAMPLING TIME
7
Exponential filter, T (63 %) = 8x SAMPLING TIME
8
Exponential filter, T (63 %) = 16x SAMPLING TIME