Instructions

Dx350_05a_oi_e.doc / Mai-18 Seite 26 / 51
Continuation Mode Counter“:
BATCH MODE
Setting of the batch counter.
The function of batch counting according to a preset value (PRESELECTION 1... 3) is only possible with the switch
condition automatic reset to zero (RESULT <= PRES-> 0) or set the counter value (RESULT <=0-> SET).
The PRESELECTION 4 is the preset value of the batch counter, when the BATCH MODE is active.
For example: If the batch counter should increment 1 all 1000 pulses, the value e.g. PRESELCTION 1 has to be set to
1000, the corresponding switch condition MODE 1 to "RESULT>=PRES->0" and BATCH MODE to INCREMENT BATCH.
Should an output be turned on after a batch amount of 33, PRESELECTION 4 has to be set to 33 and the switching
condition of MODE 4 has to be set to display value greater than or equal (RESUL>=PRES).
0
OFF
No batch counter
1
INCREMENT BATCH
increment batch counter
2
DECREMENT BATCH
decrement batch counter
3
USE INPUTS ONLY
increment / decrement batch counter only by external commands
(see command menu)
BATCH SET VALUE
In case of a reset/set command (via keyboard, control input or PC user interface) the batch counter is
set to the BATCH SET VALUE. The parameter is only visible when BATCH MODE is active.
0
Smallest value
99999999
Highest value
5.6 Mode Velocity
In this menu the operation as a runtime measurement for speed is defined.
Input A is the start input and Input B is the stop input. This menu is only displayed when the appropriate
OPERATIONAL MODE in GENERAL MENU is selected.
START / STOP
Setting the start and stop condition.
RISE TO RISE
Start = rising edge at input A
Stop = rising edge at input B
FALL TO FALL
Start = falling edge at Input A
Stop = falling edge at Input B
RISE TO FALL
Start = rising edge at input A
Stop = falling edge at Input B
FALL TO RISE
Start = falling edge at Input A
Stop = rising edge at input B
DISPLAY VALUE
Desired value, which should be displayed at the setting of BASE TIME (S).
1
Smallest value
1000
Default value
999999
Highest value