Continuation „Serial Menu”:
SERIAL PROTOCOL
Determines the sequence of characters send, when using the serial output for cyclic data transmission under time
control (xxxxxxx = value SERIAL VALUE).
Setting „1“ removes the unit address from the string which allows a slight faster transmission cycle.
0
Transmission report = Unit Nr., +/-, data, LF, CR
1
1
+/-
X
X
X
X
X
X
X
LF
CR
1
Transmission report = +/-, data, LF, CR
+/-
X
X
X
X
X
X
X
LF
CR
SERIAL TIMER (S)
This register determines the cycle time in seconds for cycling transmission of SERIAL VALUE when using the serial
output. (On a serial request, the cycling transmission is stopped for 20 s)
0.000
All cyclic transmission is switched off. The unit will send data upon a serial request or
with command SERIAL PRINT.
60.000
Cycle time in seconds.
SERIAL VALUE
This parameter defines the value to be transmitted.
Setting
Code
Register contents
0
:0
Measurement_Result
1
:1
Speed_Value
2
:2
Time_Result
3
:3
Counter
4
:4
Velocity_Speed
5
:5
Batch_Counter
6
:6
Minimal_Value
7
:7
Maximal_Value
8
:8
N.A.
9
:9
N.A.
MODBUS
This parameter enables the Modbus protocol and determines the Modbus address.
For details of the Modbus communication please refer to the additional manual MB350
0
Modbus disabled
Serial interface is using Lecom protocol (Motrona default protocol)
1 … 247
Modbus enabled: Serial interface is using Modbus RTU protocol
The set value is the Modbus address of the device.