IX34510b_e.doc / Mrz-13 Page 18 / 43
4.3. Additional Parameters for the Analogue Output
(model IX 346)
The following additional settings for the analogue output appear in the Basic Menu:
Menu
Setting Range
Default
Analogue Characteristics
You can set the following output options:
+/- 10 V (bipolar),
0 - 10 V (positive only),
4 - 20 mA
0 - 20 mA.
With setting +/-10 Volts the polarity of the output
voltage will follow the sign in the display
Analogue Offset:
Set this parameter to 0 when you expect your
analogue signal to start with 0 V (or 0 mA / 4 mA
respectively). Where another zero definition is
desired it can be set by this parameter. Setting of
e.g. 5.000 will already produce 5 volts with the
output in zero state.
-9,999..+9,999 0,000
Analogue Gain
:
Parameter to set the analogue output swing. Setting
10.00 will allow full swing of 10 V or 20 mA, setting
8.00 will reduce the swing to 8 V or 16 mA.
00,00..99,99 10,00
The following Operational Parameters provide scaling of the analogue output:
Menu
Setting Range
Default
Analogue
-
Begin
Start value of the analogue conversion range
-199999...999999 0
Analogue
-
End
End value of the analogue conversion range
-199999...999999 100000
By means of these two parameters any window of the whole display range can be mapped onto
the analogue output.