User manual
IX34510b_e.doc / Mrz-13 Page 23 / 43
The following Operational Parameters provide configuration of the serial interface:
Menu
Setting Range
Default
Serial Timer:
Setting 0,000 allows manual activation of a serial data
transmission at any time. All other settings specify the cycle
time for automatic transmission, when the interface is set to
"Printer Mode"
0,000
0,010 sec
…
9.999 sec
0,100 sec
Between two transmission cycles the unit will allow a pause
depending on the baud rate. The minimum cycle times for
timer transmissions are shown in the table.
Baud Rate Minimum Cycle Time [ms]
600 384
1200 192
2400 96
4800 48
9600 24
19200 12
38400 6
Serial Mode:
PC: Operation according to communication profile
(see 4.5.1)
Print1: Transmission of string type 1 (see 4.5.2)
Print2: Transmission of string type 2 (see 4.5.2)
Serial Register-Code:
100
...
120
101
Specifies the register code of the data to be transmitted.
The most important register codes are:
Register S-Code ASCII Description
Original SSI
Value
111 ; 1 Direct encoder data
SSI Value 113 ; 3 Encoder data after
Bit Blanking
Display
value
101 : 1 Value with full scaling
as it appears in the
display