Ix350_02b_oi_e.doc / Mai-18 Page 26 / 50
Continuation Preselection 1 Menu“:
HYSTERESIS 1
This parameter defines the switching hysteresis of the switch-off point for preselection 1
0
No switching hysteresis
99999
Switching hysteresis of 99999
PULSE TIME 1 (S)
Duration of output pulse for the switching condition of preselection 1
0,000
No output pulse (static signal)
60,000
Pulse duration of 60 seconds
OUTPUT TARGET 1
Assignment of an output or relay for the switching condition of preselection 1.
If more than one switching condition is assigned to one output / relay, the output is set when at least one
switching condition is true
0
NO
No assignment
1
CTRL OUT 1
Switching condition assigned to “Ctrl. Out 1”
2
CTRL OUT 2
Switching condition assigned to “Ctrl. Out 2”
3
CTRL OUT 3
Switching condition assigned to “Ctrl. Out 3”
4
CTRL OUT 4
Switching condition assigned to “Ctrl. Out 4”
5
RELAY 1
Switching condition assigned to “Rel. 1
6
RELAY 2
Switching condition assigned to “Rel. 2
OUTPUT POLARITY 1
Polarity for the switching condition of preselection 1
0
ACTIVE HIGH
Switching condition is true Active „HIGH“
1
ACTIVE LOW
Switching condition is true Active „LOW“
OUTPUT LOCK 1
Latch for the switching condition of preselection 1
0
NO
No latch for preselection
1
YES
Latch for preselection (command LOCK RELEASE will clear latch)