Service manual

Repair Section
49
8.7 Inspection of Fan Motor
Measure resistance across the terminals of the
fan motor. (All terminals must be disconnected
from the unit.)
Between terminals (at 77 °F (25 °C))
- J6-CF1 Approx. 6.8 ohm
- J6-CF2 Approx. 10.5 ohm
- CF1-CF2 Approx. 19.0 ohm
If the measured resistance is not equal to these
standard values, replace the fan motor.
8.8 Inspection of Compressor Motor
Measure resistance across the terminals of the
compressor motor. (All terminals must be
disconnected from the unit.)
Between terminals (at 77 °F (25 °C))
- R-C Approx. 0.9 ohm
- C-S Approx. 2.0 ohm
- S-R Approx. 2.9 ohm
If the measured resistance is not equal to these
standard values, replace the compressor. The
overload relay is internal to the compressor.
8.9 Inspection of Wiring Connection
Refer to the Wiring Diagrams on page 20 and check for connection of each wire.
8.10 Inspection of Thermistor
Using an Ohm-meter, check the resistance value across the 2-pin connector. At normal
temperature (77 °F (25 °C)) either thermistor (room or freeze) should measure approximately
10k ohm.
I002198
CF1 (White)
CF2 (Brown/White)
J5 Low (Red)
J6 High (Black)
Ground
(Green/Yellow)
I001810
C
S
R
T1
T2
T3