Operation Manual

MODEL NAME CLIMATE PRO D12 CLIMATE PRO D18
Electronic Features Control Programmable Programmable
Cooling Capacity
Rating Conditions:
Cooling:
80°F DB, 67°F WB
(Indoor and outdoor)
11,450 Btu/h 15,500 Btu/h
Heating:
70°F DB, 60°F WB (indoor)
47°F DB, 43°F WB (outdoor)
9,900 Btu/h 13,100 Btu/h
Electrical
Characteristics
Voltage Requirement 115V, 1Phase, 60Hz 115V, 1Phase, 60Hz
Total Power Consumption:
Cooling 1.38 kW 1.56 kW
Heating 1.25 kW 1.31 kW
Current Consumption:
Cooling 12.4 amps 13.8 amps
Heating 11.3 amps 11.7 amps
Recommended Fuse Size 15 amps 20 amps
NEMA Plug Confi guration 5-15 5-20
Min. - Max. Voltage 104 -127 104 -127
Fans: Motor Output
Indoor 0.06 kW 0.06 kW
Outdoor 0.12 kW 0.12 kW
Indoor Heat Exchanger
Fan Type Centrifugal Centrifugal
Max. Air Flow (hi/mid/low) 420/340/280 CFM 540/440/350 CFM
Max. External Static Pressure
0.31 IWG 0.31 IWG
Outdoor Heat
Exchanger
Fan Type Centrifugal Centrifugal
Max. Air Flow 760 CFM 825 CFM
Max. External Static Pressure
0.19 IWG 0.19 IWG
Compressor
Type Hermetic Rotary Hermetic Rotary
Output 0.75 kW 0.90 kW
74
TECHNICAL SPECIFICATIONS
Specifi cations are subject to change without notice.