Operation Manual
Table Of Contents
- SERIAL NUMBER LOCATION
- TABLE OF CONTENTS
- SAFETY PRECAUTIONS
- NAMES OF PARTS
- NOZZLES
- CONTROL PANEL
- INSTALLATION
- INITIAL SETTINGS
- OPERATION
- COOL MODE
- FAN ONLY MODE
- SCHEDULE MODE
- STARTING SCHEDULE MODE OPERATION
- STOPPING SCHEDULE MODE OPERATION
- TEMPORARY STOP DURING SCHEDULE MODE
- SETTING / EDITING / VIEWING SCHEDULE
- CLEARING SCHEDULE
- ADJUSTING BRIGHTNESS
- FAN MODE
- CHANGING TEMPERATURE SCALE
- KEY LOCK
- KEY UNLOCK
- TEMPORARY STOP DURING KEY LOCK
- SERVICE INFORMATION
- SELF-DIAGNOSTIC CODES
- LIST OF SELF-DIAGNOSTIC CODES
- EMPTYING THE DRAIN TANK
- CONDENSATE PUMP KIT (OPTIONAL ACCESSORY)
- MAINTENANCE
- TECHNICAL SPECIFICATIONS
- TROUBLESHOOTING
- WARRANTY STATEMENT
- DATA PRIVACY DISCLOSURE
MODEL NAME CLIMATE PRO X26
Electronic Features Control Programmable
Cooling Capacity
Rating Conditions: 95°F, 60% RH
24,000 Btu/h
Electrical
Characteristics
Voltage Requirement 208/230V, 1Phase, 60Hz
Total Power Consumption 2.7 kW
Current Consumption 12.4 amps
Recommended Fuse Size 20 amps
NEMA Plug Confi guration 6-20
Min. - Max. Voltage 198 -253
Fans Motor Output 0.56 kW
Evaporator
Fan Type Centrifugal
Max. Air Flow (hi/mid/low) 700/650/595 CFM
Max. External Static Pressure
0.42 IWG
Condenser
Fan Type Centrifugal
Max. Air Flow (hi/mid/low) 1475/1370/1260 CFM
Max. External Static Pressure
0.25 IWG
Compressor
Type Hermetic Rotary
Output 1.5 kW
Refrigerant Type R-410A
Dimensions W x D x H 22 x 29 x 51 in
Weight Net / Shipping 216/256 lb
Power Cord
Gauge 12 AWG (3-core)
Length 6
Condensate Tank Capacity 5 gal
Operating Conditions
Min. 70°F (@ 50% RH)
Max. 113°F (@ 50% RH)
Max. Duct Length
Per Cold Duct Hose 60
Hot Duct Hose 45
Max. Sound Level
With Duct (hi/mid/low) 66/65/64 dB(A)
Without Duct (hi/mid/low) 69/68/67 dB(A)
77
TECHNICAL SPECIFICATIONS
Specifi cations are subject to change without notice.