6.5 Compressor Motor
The compressor motor is a single-phase motor and is contained within the same housing as the
compressor.
Specifications:
- Rated Voltage: 208/230 V, 60 Hz
- Rated Output : 2300 W (at 230 V)
< NOTE >
An internal overload relay is used to protect the fan motors and the compressor motor. This relay
is built into the fan motors and compressor motor. It interrupts the flow of current when there is an
over current situation or if abnormally high temperature builds up in the fan motors and
compressor motor.
6.6 Power Cord with LCDI
Office Pro 36 is equipped with a UL approved LCDI cord and an approved NEMA plug
configuration (6-30). The appropriate outlet must be used for this plug type. LCDI is used for
monitoring leakage current. Once leakage current is detected, LCDI de-energizes the unit.
I002284
Reset Button
Test Button
<Type 1>
I002285
<Type 2>
Molded Plug, NEMA 6-30P
Reset ButtonTest Button