ioThinx 4500 (45M) Module Series User’s Manual Edition 1.0, November 2018 www.moxa.com/product © 2018 Moxa Inc. All rights reserved.
ioThinx 4500 (45M) Module Series User’s Manual The software described in this manual is furnished under a license agreement and may be used only in accordance with the terms of that agreement. Copyright Notice © 2018 Moxa Inc. All rights reserved. Trademarks The MOXA logo is a registered trademark of Moxa Inc. All other trademarks or registered marks in this manual belong to their respective manufacturers.
Safety Symbols DANGER Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a moderate-risk, potentially hazardous situation which, if not avoided. CAUTION Indicates a low-risk, potentially hazardous situation which, if not avoided, may result in minor or moderate injury. NOTE Indicates a potential malfunction which, if not avoided, however, will not result in damage to property.
Table of Contents 1. Preface .............................................................................................................................................. 1-1 Revision History ................................................................................................................................. 1-2 Relevant Models ................................................................................................................................. 1-2 Package Checklist ................
1 1. In this document, we explain the scope of and how to use this document.
ioThinx 4500 (45M) Module Series Preface Revision History Version Change Date V1.0 First Release 2018-11-09 Relevant Models This document applies to the following 45M modules: Model Name Features Operating Temp.
ioThinx 4500 (45M) Module Series Preface Safety Precautions Observe the following safety precautions when installing or using the devices discussed in this document: DANGER Never work on the device while the power source is switched on! Disconnect all power sources to the device before performing any installation, repair, or maintenance work. DANGER To avoid causing electrical arcs, be sure that all power sources have been disconnected before removing or replacing components.
ioThinx 4500 (45M) Module Series Preface CAUTION Do not attempt to repair the device yourself. If you device needs to be repaired, return the device to Moxa’s customer service department. Attempting to repair the device yourself could invalidate the device’s warranty. Additional Resources Refer to following documents for additional information.
2 2. Product Overview In this chapter, we give an overview of each of the 45M modules.
ioThinx 4500 (45M) Module Series Product Overview Technical Data Common Specifications Physical Characteristics Connector: Removable Terminal block Wiring: 18 to 24 AWG Dimensions: 19.5 x 99.0 x 60.5 mm (0.77 x 3.90 x 2.38 in) Installation: DIN-rail mounting Environmental Limits Operating Temperature: Standard Models: -20 to 60°C (-4 to 140°F) Wide Temp.
ioThinx 4500 (45M) Module Series Product Overview 45MR-2404 Specifications Input/Output Interface Relay Channels: 4 Isolation: 3k VDC or 2k Vrms Relays Type: Form A (N.O.) power relay Contact Current Rating: Resistive load: 2 A @ 30 VDC, 250 VAC Contact Resistance: 100 milli-ohms (max.) Initial Insulation Resistance: 1000 mega-ohms (min.
ioThinx 4500 (45M) Module Series Product Overview Dry Contact: On: short to FP+ Off: open Wet Contact (DI to FP-): On: 10 to 30 VDC Off: 0 to 3 VDC I/O Mode: DI or event counter Note: Only the first 2 channels support event counter mode. Digital Outputs I/O Type: Source Voltage: 12/24 VDC Current Rating: 500 mA per channel Over-Voltage Protection: 45 VDC Short-Circuit Protection: Supported Over-Temperature Shutdown: 175°C (typical), 150°C (min.
ioThinx 4500 (45M) Module Series Product Overview 45MR-6600 Specifications Input/Output Interface RTD Channels: 6 Isolation: 3k VDC or 2k Vrms Digital Outputs Input Type: PT50, PT100, PT200, PT500 (-200 to 850°C) PT1000 (-200 to 350°C) JPT100, JPT200, JPT500 (-200 to 640°C) JPT1000 (-200 to 350°C) NI100, NI200, NI500 (-60 to 250°C) NI1000 (-60 to 150°C) NI120 (-80 to 260°C) Resistance of 310, 620, 1250, and 2200 ohms Input Impedance: 625 kilo-ohms (min.) Resolution: 0.1°C or 0.
ioThinx 4500 (45M) Module Series Product Overview Appearance Front View Physical Dimensions Unit: mm (in) 2-6
ioThinx 4500 (45M) Module Series Product Overview LED Indicators Label Usage No.
3 3. Hardware Installation In this chapter, we describe how to install the 45M modules.
ioThinx 4500 (45M) Module Series Hardware Installation Wiring I/O I/O Terminal Blocks Wire range: 18 to 24 AWG Wire strip length: 9 to 10 mm Unit: mm (in.
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-1600 (-T) Wiring Guide Description: 16 DIs, 24 VDC, PNP or dry contact Single Channel (Dry Contact): Single Channel (PNP): All Channels (PNP): 3-3
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-1601 (-T) Wiring Guide Description: 16 DIs, 24 VDC, NPN or dry contact Single Channel (Dry Contact): Single Channel (NPN): All Channels (NPN): 3-4
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-2404 (-T) Wiring Guide Description: 4 Relays, form A Single Channel (Resistive Load): Single Channel (Inductive Load): All Channels: NOTE To avoid over current damage, fuse is recommended.
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-2600 (-T) Wiring Guide Description: 16 DOs, 24 VDC, sink Single Channel: All Channels: NOTE We recommend using a fuse to avoid damage from current spikes.
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-2601 (-T) Wiring Guide Description: 16 DOs, 24 VDC, source Single Channel: All Channels: NOTE We recommend using a fuse to avoid damage from current spikes.
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-2606 (-T) Wiring Guide Description: 8 DIs, 24 VDC, PNP or dry contact, 8 DOs, 24 VDC, source Single Channel (DI dry contact/DI PNP/DO source): All Channels: NOTE We recommend using a fuse to avoid damage from current spikes.
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-3800 (-T) Wiring Guide Description: 8 AIs, 0 to 20 mA or 4 to 20 mA Single Channel (2-wire/3-wire/4-wire): All Channels: 3-9
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-3810 (-T) Wiring Guide Description: 8 AIs, -10 to 10 V or 0 to 10 V Single Channel (3-wire/4-wire): All Channels: 3-10
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-6600 (-T) Wiring Guide Description: 6 RTDs Single Channel (2-wire/3-wire/4-wire): All Channels: 3-11
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-6810 (-T) Wiring Guide Description: 8 TCs Single Channel (TC Sensor/Voltage Source): All Channels: 3-12
ioThinx 4500 (45M) Module Series Hardware Installation 45MR-7820 (-T) Wiring Guide Description: Potential distribution module Single Channel: All Channels: 3-13
ioThinx 4500 (45M) Module Series Hardware Installation Mounting the Module Take the following steps to mount the device on or unmount the device from a DIN rail. DANGER Never install the device when the power source is switched on! Installing the I/O Module on the DIN Rail Step 1: Align the I/O module side by side with the head/CPU module, making sure that the upper and lower rails are hooked together.
ioThinx 4500 (45M) Module Series INFORMATION Hardware Installation With the I/O module inserted in place, the internal bus will establish a connection through the adjacent module(s). Unmounting the I/O Module from the DIN Rail Step 1: Use your finger to lift the release tab on the lower part of the module. Step 2: Push the top of the release tab to latch it, and then pull the module out. NOTE Electrical connections for the internal bus will be disconnected when the I/O module is removed.