User Manual
- 7 -
Grounding EDS-208
Grounding and wire
routing help limit the effects
of noise due to electromagnetic interference
(EMI). Run the ground connection from the right
most contact of the 3
-contact terminal block to
the grounding surface prior to connecting
devices.
ATTENTION
This product is intended to be mounted to a well
-grounded
mounting surface such as a metal panel.
Wiring the Power Inputs
The two left-most contacts of the 3-contact terminal block connector on
EDS-208’s top panel are used for the DC input. Top and front views of
one of the terminal block connectors are shown here.
STEP 1:
Insert the negative/positive DC wires
into the V
-/V+ terminals.
STEP 2:
To keep the DC wires from pulling loose,
use a small flat
-blade screwdriver to tighten the
wire
-clamp screws on the front of the terminal
block connector.
STEP 3:
Insert the plastic terminal block
connector prongs into the terminal block
receptor, which is located on EDS’s top panel.
ATTENTION
•
Only connect to a class 2 power supply.
•
Use 60/75°C copper (CU) wire 28-12 AWG only.
• Use a maximum torque of 4.5 in-lb.