EDS-316 Series Quick Installation Guide Moxa EtherDevice Switch Edition 6.1, March 2018 Technical Support Contact Information www.moxa.
Overview The Moxa EtherDevice™ EDS-316 series of 16-port smart Ethernet switches provides an economical solution for your Ethernet connections. As an added bonus, the built-in smart alarm function helps system maintainers monitor the health of your Ethernet network. EDS-316 has a wide operating temperature range of -40 to 75°C, and is designed to withstand a high degree of vibration and shock.
Panel Layout of EDS-316 (standard-type) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13.
Panel Layout of EDS-316 (SC-type) Product models not shown here: EDS-316-S-SC is identical to EDS-316-M-SC. EDS-316-SS-SC and EDS-316-MS-SC are identical to EDS-316-MM-SC. 1. Grounding screw 2. Terminal block for power input (PWR1, PWR2) and relay output 3. Heat dissipation orifices 4. DIP switches (EDS-316 series has 18 DIP switches in total; 1 DIP switch is reserved) 5. Power input PWR1 LED 6. Power input PWR2 LED 7. Fault LED 8. 10/100BaseT(X) Port 9. TP port’s 100 Mbps LED 10. TP port’s 10 Mbps LED 11.
Panel Layout of EDS-316 (ST-type) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15.
Mounting Dimensions Unit = mm (inch) DIN-Rail Mounting The aluminum DIN-Rail attachment plate should already be fixed to the back panel of EDS-316 when you take it out of the box. If you need to reattach the DIN-Rail attachment plate, make sure the stiff metal spring is situated towards the top, as shown in the figures below. STEP 1: Insert the top of the DIN-Rail into the slot just below the stiff metal spring. STEP 2: The DIN-Rail attachment unit will snap into place as shown below.
Wall Mounting (optional) For some applications, you will find it convenient to mount EDS-316 on the wall, as illustrated in the figure. STEP 1: Remove the aluminum DIN-Rail attachment plate from EDS-316’s rear panel, and then attach the wall mount plates, as shown in the figure. STEP 2: Mounting EDS-316 on the wall requires 4 screws. Use the switch, with wall mount plates attached, as a guide to mark the correct locations of the 4 screws. The heads of the screws should be less than 6.
WARNING EXPLOSION HAZARD – Servicing, replacing, and installing the product can only take place is an area that is non-hazardous. ATEX Information 1. 2. 3. 4. 5. 6.
WARNING Substitution of components may impair suitability for Class I, Division 2, and Zone 2. These devices must be supplied by an SELV source as defined in Low Voltage Directive 73/23/EEC and 93/68/EEC. WARNING This unit is a built-in type. When the unit is installed in another piece of equipment, the equipment enclosing the unit must comply with fire enclosure regulation IEC 60950/EN60950 (or similar regulation).
ATTENTION This product is intended to be mounted to a well-grounded mounting surface, such as a metal panel. Wiring the Alarm Contact The Alarm Contact consists of the two middle contacts of the terminal block on EDS’s top panel. You may refer to the next section for detailed instructions on how to connect the wires to the terminal block connector, and how to attach the terminal block connector to the terminal block receptor.
ATTENTION • Conductors suitable for use in an ambient temperature of 93°C must be used for the power supply terminal. • One individual conductor in a clamping point with 28-12 AWG wire size, and a torque value of 4.5 lb-in should be used. ATTENTION Transient provisions shall be provided to limit the peak rated voltage to a maximum of 140% of the peak rated voltage.
RJ45 (8-pin) to RJ45 (8-pin) Cross-Over Cable Wiring 100BaseFX Ethernet Port Connection The concept behind the SC/ST port and cable is very straightforward. Suppose you are connecting devices I and II. Contrary to electrical signals, optical signals do not require a circuit in order to transmit data. Consequently, one of the optical lines is used to transmit data from device I to device II, and the other optical line is used transmit data from device II to device I, for full-duplex transmission.
Alarm Contact WARNING Exposure to some chemicals may degrade the sealing properties of materials used in the Sealed Relay Device. Moxa EtherDevice Switch has one Alarm Contact located on the top panel. For detailed instructions on how to connect the Alarm Contact power wires to the two middle contacts of the 6-contact terminal block connector, see the Wiring the Alarm Contact section on page 7. A typical scenario would be to connect the Fault circuit to a warning light located in the control room.
LED Color PWR1 AMBER PWR2 AMBER FAULT RED 10M GREEN 100M (TP) GREEN 100M (FX) GREEN State On Description Power is being supplied to power input PWR1 Power is not being supplied to power input Off PWR1 On Power is being supplied to power input PWR2 Power is not being supplied to power input Off PWR2 When the corresponding PORT alarm is On enabled, and the port’s link is inactive.
The 100 Mbps fiber ports are switched ports, and perform as a domain, providing a high bandwidth backbone connection that supports long fiber cable distances (up to 5 km for multi-mode, and 40 km, and 80 km for single-mode) for installation versatility. Dual Speed Functionality and Switching Moxa EDS-316’s 10/100 Mbps switched RJ45 port auto negotiates with the connected device for the fastest data transmission rate supported by both devices.
If an EDS-316 RJ45 Ethernet port is connected to a non-negotiating device, it will default to 10 Mbps speed and half-duplex mode, as required by the IEEE 802.3u standard. Specifications Technology Standards Forward and Filtering Rate Packet Buffer Memory Processing Type Address Table Size Interface RJ45 Ports Fiber Ports LED Indicators DIP Switch Alarm Contact IEEE802.3, 802.3u, 802.3x 148810 pps (100M), 14881 pps (10M) 1.25 Mbit Store and Forward, with IEEE802.
Power Input Voltage Input Current @ 24 VDC Connection Overload Current Protection Reverse Polarity Protection Inrush Current 12/24/48 (9.6 to 60) VDC, redundant inputs 0.34 A (EDS-316) 0.35 A (EDS-316-S-SC) 0.35 A (EDS-316-M-SC, EDS-316-M-ST) 0.40 A (EDS-316-SS-SC) 0.39 A (EDS-316-MM-SC, EDS-316-MM-ST) Removable “6-pin” Terminal Block Present Present Max. 6.3A @ 24VDC (0.1 - 1ms) Mechanical Casing IP30 protection, metal case Dimensions 80.5 x 135 x 105 mm (W x H x D) Weight 0.
Ordering Information Ordering Code Definition EDS-316-AA-BB[-CC][-T] Fiber Port FO Connector M: S: MM: SS: MS: SC: SC Connector ST: ST Connector 1 1 2 2 1 1 Multi-mode Single Mode Multi-mode Single Mode Multi-mode, Single Mode Transmission Operating distance Temperature 80: 80 km -T: Wide operating Temp.