- 16 -
Rese t But t on
There are t wo funct ions available on t he Reset But t on. One is t o r eset
the Ethernet swit ch to fact or y default set tings by pressing and holding
the Reset but t on for 5 seconds. Use a point ed obj ect , such as a
st raight ened paper clip or t oothpick , t o depress t he Reset but t on. This
will cause the STATE LED t o blink once a second. Aft er depressing th e
but ton for 5 cont inuous seconds, t he STATE LED will st art t o blink
rapidly. This indicat es t hat fact ory default sett ings have been loaded
and you can r elease t he reset but t on. The ot her funct ion is t o reboot
the device by depressing reset but t on for less t han five seconds.
Tur b o Ring D I P Sw itch Set t ings
The EDS devices are plug- and-play m anaged r edundant Ethernet
sw it ches. The propr iet ar y Turbo Ring prot ocol was developed by Moxa
to pr ovide bet t er network reliabilit y and fast er recovery t im e. Moxa
Turbo Ring’s recover y t im e is less t han 50 m s ( Turb o Ring V2 ) —
com pared t o a 3- t o 5- m inute recovery tim e for com m er cial swit ches—
decreasing t he possible loss caused by net work failur es in an indust rial
set t ing.
Ther e ar e five Hardware DI P Switches for Turbo Ring on t he bott om
panel of t he EDS device t hat can help setup t he Turbo Ring easily
within seconds. I f you do not want t o use a hardw are DI P swit ch t o
set up t he Turbo Ring, y ou can use a web browser, t elnet , or console t o
disable this funct ion.
N OTE
Please refer to the Tu rb o Ring sect ion in User's Manual for
m ore det ail infor m
at ion about the set t ing and usage of Tur bo
Rin g V2 .
Turbo Ring D I P Sw itch Se t t ings
The default setting for each DI P Switch is OFF. The
follow ing t able explains t he effect of set ting t he DI P
Sw it ch to t he ON posit ion
.
Rem ove t he rubber cover on t he
bot tom panel of
the device
t o expose t he DI P sw it ches.
DI P Sw it ch Se t t ing s
DI P 1
DI P 2
DI P 3
DI P 4
DI P 5
Reserved
for fut ur e
use
ON : Enables the
default “ Ring
Coupling
( backup) ” port
when DI P sw it ch 4
is already enabled.
ON : Enables
this EDS as
the Ring
Mast er .
ON :
Enables t he
default
“ Ring
Coupling”
port .
ON : Act ivates
DI P sw it ch 2,
3, and 4 to
configu re
Turbo Ring V2
set t ings.
OFF:
Enables t he
default Ring
Coupling ( pr im ary )
por t w hen DI P
sw it ch 4 is alr eady
enabled.
OFF:
This
EDS will not
be the Rin g
Mast er .
OFF:
This
EDS will not
be the Rin g
Coupler .
OFF:
DI P
sw it ch 2, 3,
and 4 w ill be
disabled.