User Manual

- 9 -
ATEX/IECEx Information
1. Certificate number: ATEX: DEMKO 18 ATEX 1978X
IECEx: IECEx UL 18.0089X (For EDS-408A copper and 2 Fiber model
only)
2. Ambient range:
-40°C ≤ Tamb ≤ 75°C for model with suffix T only
-10°C ≤ Tamb ≤ 60°C for model without suffix T only
3. Certification string:
ATEX:
EDS-405A Series: Ex nA nC IIC T4 Gc
EDS-408A Series (Copper Model EDS-408A(-T)):
Ex nA nC IIC T4 Gc
EDS-408A Series (2 Fiber Models EDS-408A-MM/SS(-T)):
Ex nA nC op is IIC T4 Gc
IECEx:
EDS-408A(-T), EDS-408A-MM/SS(-T): Ex nA nC IIC T4 Gc
4. Standards covered:
EN 60079-0:2012+A11:2013, IEC 60079-0 Ed.6,
EN 60079-15:2010, IEC 60079-15 Ed.4,
EN 60079-28:2015, IEC 60079-28 2
nd
version
5. The conditions of Safe usage for IECEx/ATEX (Zone2):
Provisions shall be made to provide the transient protection to
be set at a level not exceeding 140% of the peak rated voltage.
These devices shall be mounted in a suitable tool-accessible
ATEX/IECEx Certified enclosure rated to at least IP54 as defined
in EN/IEC 60529 and Pollution Degree 2 as defined in EN/IEC
60664-1, and used within their rated electrical and
environmental ratings.
6. The conditions of safe usage for other environments
These products must be mounted in an IP54 enclosure.
Install in an area of pollution degree 2 or less.
Use a conductor wire of size 0.2 mm² or greater.
Input Terminal Block (JP3, JP4) - Rated 300 V/12 A, solder on
the board, mating with plug-half connector suitable for 28-12
AWG (Sol, Str) wire size, torque value 4.5-5.0 lb-in. The
plughalf connection has a latching mechanism.
Subject devices are to use conductors suitable for 95°C and
must be used for the Power Supply Terminal.