User`s manual

ioLogik E1200 Series Introduction
1-5
ioLogik E1210
Inputs and Outputs
Digital Inputs:
16 channels
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact:
NPN (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
PNP (DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type:
8 points per COM
Counter Frequency:
250 Hz, power off storage
Digital Filtering Time Interval:
Software selectable
Power Requirements
Power Consumption:
110 mA @ 24 VDC
MTBF
(mean time between failures)
Time:
671,345 hrs
Database:
Telcordia (Bellcore)
ioLogik E1211
Inputs and Outputs
Digital Outputs:
16 channels
Isolation:
3K VDC or 2K Vrms
Digital Output
Type:
Sink
I/O Mode:
DO or Pulse Output
Pulse Output Frequency:
500 Hz
Over
-voltage Protection: 45 VDC
Over
-current Protection: 2.6 A (4 channels @ 650 mA)
Over
-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating:
200 mA per channel
Power Requirements
Power Consumption:
208 mA @ 24 VDC
MTBF (mean time between failures)
Time:
923,027 hrs
Database:
Telcordia (Bellcore)