User`s manual

ioLogik E1200 Series Introduction
1-7
ioLogik E1213
Inputs and Outputs
Digital Inputs:
8 channels
Digital Outputs:
4 channels
Digital Input/Output (configurable by jumper):
4 channels
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type:
NPN, PNP, and dry contact
I/O Mode:
DI or event counter
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact:
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Common Type:
12 points per COM
Counter/Frequency:
250 Hz, power off storage
Digital Output
I/O Mode:
DO or Pulse Output
I/O Type:
Source
Current:
500 mA per channel
Voltage:
15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4 DO channels)
Pulse Wave Width/Frequency:
1 ms/500 Hz
Over
-Voltage Protection: 45 VDC
Over
-Current Limit: 1.5 A per channel @ 25°C
Over
-Temperature Shutdown: 175°C (typical), 150°C (min.)
Output Current Rating:
0.5A per channel
Power Requirements
Power Input:
24 VDC nominal, 12 to 36 VDC
Power Consumption:
130 mA typical @ 24 VDC