User`s manual

ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-9
Reference Address Data Type Description
00284 0x011B 1 bit CH11 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00285 0x011C 1 bit CH12 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00286 0x011D 1 bit CH13 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00287 0x011E 1 bit CH14 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00288 0x011F 1 bit CH15 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
04129 0x1020 1word CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04130 0x1021 1word CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04131 0x1022 1word CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04132 0x1023 1word CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04133 0x1024 1word CH4 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04134 0x1025 1word CH5 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04135 0x1026 1word CH6 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04136 0x1027 1word CH7 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04145 0x1030 1 bit Clear Watchdog Alarm