User`s manual

ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-23
Reference Address Data Type Description
2: Over Range
3. Under Range
30580 0x0243 1 word Read AI 3 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
40033 0x0020 1 word DO all Value (Ch03)
Bit0 = Ch0 DO Value (0=OFF, 1=ON)
Bit3 = Ch3 DO Value (0=OFF, 1=ON)
Bit4 to 15 = reserved
40545 0x0220 1 word CH0 AI 0 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40546 0x0221 1 word CH0 AI 1 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40547 0x0222 1 word CH0 AI 2 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40548 0x0223 1 word CH0 AI 3 Mode: 1:4-20mA, 2:0-20mA, 4:BO
40561 0x0230 2 words CH AI 0 BO Value (floating point)
40563 0x0232 2 words CH AI 1 BO Value (floating point)
40565 0x0234 2 words CH AI 2 BO Value (floating point)
40567 0x0236 2 words CH AI 3 BO Value (floating point)
E1260 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
04145 0x1030 1 bit Clear Watchdog Alarm
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
31537 0x0600 1 word CH0 Read RTD Value
Range 065535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31538 0x0601 1 word CH1 Read RTD Value
Range 065535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31539 0x0602 1 word CH2 Read RTD Value
Range 065535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31540 0x0603 1 word CH3 Read RTD Value
Range 065535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31541 0x0604 1 word CH4 Read RTD Value
Range 065535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31542 0x0605 1 word CH5 Read RTD Value
Range 065535, Unit:0.1 (Ohm, Celsius, Fahrenheit)