Datasheet

www.moxa.com
3
Sensor Type ioLogik E2210 Series: Dry Contact and Wet Contact (NPN)
ioLogik E2212/E2214/E2242 Series: Dry Contact and Wet Contact (NPN or PNP)
Wet Contact (DI to GND) On: 0 to 3 VDC
Off: 10 to 30 VDC
Digital Outputs
Connector Screw-fastened Euroblock terminal
Current Rating 200 mA per channel
I/O Mode DO or pulse output
I/O Type Sink
Over-Current Protection 0.65 A per channel @ 25°C
Over-Temperature Shutdown 175°C (min.)
Over-Voltage Protection 45 VDC (typical)
Pulse Output Frequency 1 kHz
DIO Output Leakage Current 4.0 mA @ 24 VDC
Relays
Connector Screw-fastened Euroblock terminal
Contact Current Rating Inductive load: 2 A @ 30 VDC, 250 VAC, 110 VAC
Resistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Contact Resistance 100 milli-ohms (max.)
Electrical Endurance 100,000 operations @ 5 A resistive load
Mechanical Endurance 1,000,000 operations
Minimum Permitted Load 1 A @ 5 VDC
Pulse Output Frequency 0.3 Hz at rated load
Type Form A (N.O.) power relay
I/O Mode Relay or pulse output
Note Ambient humidity must be non-condensing and remain between 5 and 95%. The relays
may malfunction when operating in high condensation environments below 0°C.
Analog Inputs
Accuracy ioLogik E2240/E2242:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
ioLogik E2240-T/E2242-T:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
±0.5% FSR @ -40 to 75°C
Connector Screw-fastened Euroblock terminal
I/O Mode Voltage/Current
I/O Type Differential
Input Impedance ioLogik E2240 Series: 900 kilo-ohms (min.)
ioLogik E2242 Series: 200 kilo-ohms (min.)