User`s manual

ioLogik Active Ethernet Modular User’s Manual Using Modbus/TCP
B-13
DO Module Configuration Map:
N stands for channel quantity
Input register map(R)
Addrss offset Access Word Description
0x0000
Read-only
1 Moxa code, (If M-2801, the value is 0x2801)
0x0001~0x0002 Read-only 2 Reserved
0x0003 Read-only 1 Number of channels
0x0004 Read-only 1 Channel occupied list. (bit-wise)
0x0005 Read-only 1 Firmware version
Holding register map (R/W)
Addrss offset Access Word Description
0x0000~8N-1 R/W N*8 Channel alias name (Alias Name is 8 word)
8N~16N-1 R/W N*8 Alias for ON status (Alias Name is 8 word)
16N~24N-1 R/W N*8 Alias for OFF status (Alias Name is 8 word)
Coil map (R/W)
Addrss offset Access Bit Description
0x0000~N-1 R/W N Safe mode action (0:fault value, 1:hold last state)
N~2N-1 R/W N Fault value
2N~3N-1 R/W N Power-on status
DI Module Configuration Map:
N stands for channel quantity
Input register map(R)
Addrss offset Access Word Description
0x0000
Read-only
1 Moxa code, (If M-2801, the value is 0x2801)
0x0001 to 0x0002 Read-only 2 Reserved
0x0003 Read-only 1 Number of channels
0x0004 Read-only 1 Channel occupied list. (bit-wise)
0x0005 Read-only 1 Firmware version
Holding register map(R/W)
Addrss offset Access Word Description
0x0000 to 8N-1 R/W N*8 Channel alias name (Alias Name is 8 word)
8N to 16N-1 R/W N*8 Alias for ON status (Alias Name is 8 word)
16N to 24N-1 R/W N*8 Alias for OFF status (Alias Name is 8 word)