Datasheet

1
www.moxa.com
info@moxa.com
Remote I/O
ioLogik R1200 Series
RS-485 remote I/O
Dual RS-485 remote I/O with built-in repeater
Supports the installation of multi-drop communication parameters
Install communication parameters and upgrade firmware via USB
Upgrade firmware through an RS-485 connection
Wide operating temperature (-40 to 85°C) models available
The ioLogik R1200 smart RS-485 serial remote I/O devices are perfect
for establishing a cost-effective, dependable, and easy-to-maintain
process control remote I/O system. Serial remote I/O products offer
process engineers the benefit of simple wiring, as they only require
two wires to communicate with the controller and other RS-485
devices while adopting the EIA/TIA RS-485 communication protocol
to transmit and receive data at high speed over long distances. In
addition to communication configuration by software or USB and
dual RS-485 port design, Moxa’s smart remote I/O devices eliminate
the nightmare of extensive labor associated with the setup and
maintenance of data acquisition and automation systems. Moxa also
offers different I/O combinations, which provide greater flexibility and
are compatible with every kind of application.
Introduction
ioLogik R1200 Series Selection Table
Models
I/O Combinations
Digital Inputs Configurable DI/Os Analog Inputs Analog Outputs Relay Outputs
ioLogik R1210
16
ioLogik R1212
8 8
ioLogik R1214
6 6
ioLogik R1240
8
ioLogik R1241
4
ioLogik R1210 Specifications
Inputs and Outputs
Digital Inputs: 16 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to COM):
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type: 8 points per COM
Counter Frequency: 2.5 kHz
Digital Filtering Time Interval: Software Configurable
Power Requirements
Power Consumption: 154 ma @ 24 VDC
ioLogik R1212 Specifications
Inputs and Outputs
Digital Inputs: 8 channels
Configurable DI/Os: 8 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open

Summary of content (3 pages)