User Manual

- 3 -
175°C (typical), 150°C (min.)
200 mA per channel
3K VDC or 2K Vrms
Relay Output
Form A (N.O.) relay outputs, 5A
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC
2 A
5 A
500 VAC
1500 ms (Max.)
1G min. @ 500 VDC
100,000 times (Typical)
Initial Contact
30 milli-ohms (Max.)
0.3 Hz at rated load
Analog Input
Differential input
16 bits
Voltage / Current
0 to 10 VDC, 4 to 20 mA
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
12 samples/sec
10M ohms (minimum)
120 ohms
Analog Output
12 bits
0 to 10 VDC, 4 to 20 mA
10 mA (Max.)
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
• Internal power: 400 ohms
• External 24V power: 1000 ohms
Installation
Jumper Settings
The models with DIO or AI channels require configuring the jumpers
inside the enclosure. Remove the screw located on the back panel and
open the cover to configure the jumpers.
DIO mode configuration is shown
to the right (default: DO Mode).
Analog mode configuration is
shown to the right (default:
Voltage Mode).