MGate 5111 Quick Installation Guide Version 1.1, November 2019 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777 Fax: 1-714-528-6778 Moxa China (Shanghai office): Toll-free: 800-820-5036 Tel: +86-21-5258-9955 Fax: +86-21-5258-5505 Moxa Europe: Tel: +49-89-3 70 03 99-0 Fax: +49-89-3 70 03 99-99 Moxa Asia-Pacific: Tel: +886-2-8919-1230 Fax: +886-2-8919-1231 Moxa India: Tel: +91-80-4172-9088 Fax: +91-80-4132-1045 2019 Moxa Inc.
Overview The MGate 5111 is an industrial Ethernet gateway for Modbus RTU/ASCII/TCP, PROFINET and EtherNet/IP to PROFIBUS slave network communications. Package Checklist Before installing the MGate 5111, verify that the package contains the following items: • • • MGate 5111 gateway Quick installation guide (printed) Warranty card Please notify your sales representative if any of the above items is missing or damaged.
LED Indicators LED Color PWR 1, Green PWR 2 Off Green Ready Red Description Power is on Power is off Steady on: Power is on, and the unit is functioning normally Blinking: The unit is responding to the software’s Locate function Steady on: Power is on, and the unit is booting up Blinking: Indicates an IP conflict, or the DHCP or BOOTP server is not responding properly Flashing quickly: the microSD card failed The Ethernet port is receiving or transmitting data Modbus TCP Client: Modbus communication in pro
LED PBS Eth1, Eth2 Color Green (Flashing only) Red (Steady) Off Green Amber Off Description PROFIBUS is receiving or transmitting data Error in the configuration or parameter data. PROFIBUS offline or Slave ID is wrong. Indicates an 100 Mbps Ethernet connection Indicates a 10 Mbps Ethernet connection The Ethernet cable is disconnected *Only indicates serial communication status; for Modbus TCP status, please refer to LAN LED indicator.
Wall or Cabinet Mounting Two metal plates are provided for mounting the unit on a wall or inside a cabinet. Attach the plates to the unit’s rear panel with screws. With the plates attached, use screws to mount the unit on a wall. The heads of the screws should be 5 to 7 mm in diameter, the shafts should be 3 to 4 mm in diameter, and the length of the screws should be more than 10.5 mm. For each screw, the head should be 6 mm or less in diameter, and the shaft should be 3.5 mm or less in diameter.
Modbus Serial Port (Male DB9) Pin RS-232 1 DCD 2 RXD 3 TXD 4 DTR 5* GND 6 DSR 7 RTS 8 CTS 9 – *Signal ground RS-422/ RS-485 (4W) TxD-(A) TxD+(B) RxD+(B) RxD-(A) GND – – – – RS-485 (2W) – – Data+(B) Data-(A) GND – – – – PROFIBUS Serial Port (Female DB9) Pin 1 2 3 4 5 6 7 8 9 Signal PROFIBUS D+ RTS Signal common 5V PROFIBUS D- Console Port (RS-232) The MGate 5111 Series can use an RJ45 serial port to connect to a PC to configure the device.
Specifications Power Input Power Consumption (Input Rating) Operating Temperature Storage Temperature 12 to 48 VDC 12 to 48 VDC, 416 mA (max.) Standard Models: 0 to 60°C (32 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) -40 to 85°C (-40 to 185°F) ATEX and IECEx Information 1. 2. 3. 4. 5. DEMKO Certificate number: 17 ATEX 1848X IECEx Certificate number: IECEx UL 17.
WARNING EXPLOSION HAZARD Do not disconnect the equipment unless the power has been switched off, or the area is known to be nonhazardous. WARNING EXPLOSION HAZARD The substitution of any components may impair suitability for Class 1, Division 2. WARNING EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE FOLLOWING DEVICE: Sealed Relay Device U21. WARNING EXPLOTION HAZARD Indoor use and Pollution degree 2.