Datasheet

www.moxa.com
1
TCC-120/120I Series
Industrial RS-422/485 converters/repeaters with optional 2 kV isolation
Features and Benefits
Boosts serial signal to extend transmission distance
Wall mounting or DIN-rail mounting
Terminal block for easy wiring
Power input from terminal block
DIP switch setting for built-in terminator (120 ohm)
Boosts RS-422 or RS-485 signal, or converts RS-422 to RS-485
2 kV isolation protection (TCC-120I)
Certifications
Introduction
The TCC-120 and TCC-120I are RS-422/485 converters/repeaters designed to extend RS-422/485 transmission distance. Both products have a
superior industrial-grade design that includes DIN-rail mounting, terminal block wiring, and an external terminal block for power. In addition, the
TCC-120I supports optical isolation for system protection. The TCC-120 and TCC-120I are ideal RS-422/485 converters/repeaters for critical
industrial environments.
Specifications
Serial Interface
Connector Terminal block
No. of Ports 2
Serial Standards RS-422, RS-485
Baudrate 50 bps to 921.6 kbps (supports non-standard baudrates)
Isolation TCC-120I: 2 kV
Pull High/Low Resistor for RS-485 1 kilo-ohm, 150 kilo-ohms
RS-485 Data Direction Control ADDC® (automatic data direction control)
Terminator for RS-485 N/A, 120 ohms, 120 kilo-ohms
Serial Signals
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
Power Parameters
Input Current TCC-120: 65 mA @ 12 VDC
TCC-120I: 180 mA @ 12 VDC
Input Voltage 12 to 48 VDC