User Guide
75 
Symptom  Possible Cause  Action 
Heat  pump  puts  out
cool  air  in  the  heat 
mode and warm air in 
the cool mode. 
Changeover Valve is not 
configured to match the 
changeover required by the 
installed heat pump. 
Set  Changeover  Valve  (Installer 
Setup  Number  0190)  to  match 
the  changeover  required  by  the 
installed heat pump. 
Both  the  heating  and 
cooling equipment
are running at the 
same time. 
The  heating  equipment  is 
not  a  heat  pump  but  the
System  Type  is  set  to  Heat 
Pump. 
Set System Type (Installer Setup 
Number  0170)  to match the
installed  heating  and/or  cooling 
equipment. 
Heating  and  cooling  wires 
are shorted together. 
Separate the shorted heating
and cooling wires. 