iTempo Installation Manual

mr
.
steam
®
Installation & Operating Instructions
______________________________________________________________
11
5.
Route the end of the probe cable with the
temperature probe through the wall into the
steam room as shown in Diagram 2.
IMPORTANT NOTE:
Do not strain,
staple, pinch or otherwise damage the probe
cable.
6. With a minimal length of the cable exposed
apply silicone (provided) to the hole in the
wall as required to create a moisture seal as
shown in Diagram 2.
7. Push the temperature cable and probe into
hole as required to leave minimum 1/4”,
maximum 1/2” of the bulb exposed as
shown in Diagram 3.
Insure a minimum of 1/4” of
the temperature probe is exposed to the air.
Failure to do so may interfere with the ability
to sense temperature and may result in
excessive steam room temperatures.
The exposed area of the tem-
perature probe must be free of silicone or any
materials or obstructions that prevent direct
exposure to the steam room air. Failure to
do so may interfere with the ability to sense
temperature and may result in excessive steam
room temperatures
.
NOTE: For Illustrative Purposes Only.
Drawings Not to Scale
WARNING
!
WARNING
!
Silicone Sealant
Cable
Wall
1
⁄4" minimum
1
2"
maximum
DIAGRAM 2
DIAGRAM 3
Sectional View
Installed Remote
Temperature Probe
showing a minimum
of 1/4” of the probe
exposed to steam
room air
s t e a m r o o m i n t e r i o r