Installation Sheet

Linear Steam Head
3
®
®
NOTE: Drawings are for illustrative purposes only. Consult with qualified designer, architect or contractor for steam room construction.
Model 104480
2
1
8
"
9
1
4
"
1
1
16
"
5
8
"
Slotted
Mounting Holes
Slotted
Mounting Holes
14"
Figure 1
Slotted Mounting
Holes
Slotted Mounting
Holes
Steam
Outlet
3/4”
NPT
Steam Outlet Connection
14
1/16”
x 19”
9
1/4”
1
1/16”
5/8”
2
1/8”
BOX CONTENTS:
Linear Steam Head
Faceplate
Diverter
AromaTray
Silicone Sealant
Installation Instructions
Adjustment Screws
Installation Section
INSTALLATION STEPS
Because steam emissions are very hot, locate the steam head
where incidental contact by the bather with direct steam emission cannot
occur. Do not locate the steam head in any location where the steam
emission zone is near a seat, bench or any space occupied by any persons.
See Fig. 2 for a diagram of the steam emission zone. Failure to follow these
instructions may result in a hazardous condition, scalding or personal injury.
Do not install a
Linear Steam Head in a tub or
acrylic/fiberglass shower enclosure.
Failure to follow these instructions
may result in a hazardous
condition, scalding or personal
injury
STEP 1. Locate the steam head 6-
12” above the finished floor. Do
not locate the steam head in any
location where the steam emission
zone is near a seat, bench, or any
space occupied by any persons.
See Fig. 2 for a diagram of the
steam emission zone.
6"-12"
Above Floor
Steam
Emisson Zone
Steam Room
Interior
Steam
Emission
Without
Diverter
6"-12"
Above Floor
Diverter
Steam Room
Interior
Steam
Emission
Number Steam
Generator of Linear Emission
Model Steam Heads Zone
MS90-MS400 1 18”
Super1-Super3 1 24”
MX4-MX6 2 24”
Figure 2