Installation Instructions for Round & Square
iTempo
®
and iTempoPlus
®
IMPORTANT NOTE: If the desired location for the control is outside
the steam room a Remote Temperature Probe (MSTS) must be installed
inside the steam room. Contact MrSteam technical service 1-800-767-
8326 for more information on the Remote Temperature Probe.
NOTE:
The connector is keyed with the flat facing up. The control cable is the
same at both ends.
STEP 1
Determine the desired installation location of the control. The iTempo and
iTempoPlus
controls are designed to be installed inside or outside the steam
room as a matter of personal preference. If the control is installed inside the
steam room the control must be located:
• 4-5 feet above the oor near the bather seating area.
• The control features an integral temperature sensor. Locate the control in a
location representative of the desired steam bathing temperatures. Do not
locate the control above or near the steam head or direct steam emissions.
Locating the controls near the steamhead or near direct steam emissions may
result in poor steam room temperature control.
• On a vertical wall
• The control cable length is 30 feet. Insure that the control and/or steam
generator are located accordingly. Contact a MrSteam technical
service representative if a longer cable is required (60 ft. cable, PN
103990-60).
IMPORTANT NOTE:
The control cable should be run in a dedicated
1” conduit to facilitate installation and service. Be careful not to strain,
staple, pinch or otherwise damage the control cable. Route cable as
required to permit replacement. Do not route cable inside conduit
together with power lines or close to hot water or steam piping.