LOCATING THE STEAM GENERATOR
Applies to 1-6
1. Do not route iSteam, AirTempo, iTempo/Plus, iTempo OR
any control wiring inside conduit together with power lines
or close to hot water or steam piping. Doing so may result
in an inoperative or hazardous installation.
2. Installation or operation of the steam generator in an
ambient temperature above 113˚ F (45 °C) may result in a
hazardous condition or property damage.
3. Do not install the steambath generator inside steam room,
a shock hazard and/or equipment damage will occur.
4. Do not install steambath generator outdoors or
wherever environmental conditions may result in a
shock hazard and/or equipment damage.
5. To prevent a fire hazard, do not install the steambath gen-
erator near flammable or corrosive materials or chemicals
such as gasoline, paint thinners, or the like.
6. Installation in areas having high concentrations of chlorine
(such as pool equipment room) must be avoided.
Applies to 7-11
7. Do not install the steambath generator or plumbing line in
an unheated attic or any locations where water could freeze
and cause pipes to rupture and cause property damage.
8. Steam piping, safety valve, drain valve and plumbing
become hot during operation and remain hot after shut-
down for a period of time. Provide appropriate protection,
including insulating plumbing lines. Avoid plumbing runs
and steamhead locations that can come in contact with
bathers to prevent a burn hazard.
9. Install the steambath generator on a solid and level surface.
10. Install the steambath generator in an upright position only
to prevent damage to the generator, pipes and electrical
system. Failure to install in an upright position may result
in a leak or shock hazard.
11. Do not hang the MAX steam generator on a wall. Hanging
the MAX generator on a wall may result in a leak, shock
hazard or equipment damage.
Applies to 12-18
12. Provide a minimum of 18"on the left side and 21" at
the top of the steam generator or as required for
servicing. See page 7 for complete information.
13. Select a location as near as practical to the steam
room. Typical locations include heated attic or base-
ment.
14. The standard length of the cable for connecting the
control to the steam generator is 30 feet. The steam
generator and control must be located accordingly.
A 60 foot cable is available as a special order part for
iTempo
®
(PN 103990-60) and for iSteam
®
(PN 104117-
60). The maximum cable length is 60 feet.
15. Install anti-water hammer device as necessary.
16. The control cable should be run in a dedicated 1-inch
conduit to facilitate installation and service.
17. Provide unions as required to facilitate installation and
removal of the steam generator.
18. The minimum clearance from combustible surfaces is
zero all around.