CHECKING STEAM GENERATOR FOR CORRECT SIZING
Materials of construction, room size and special design features such
as large glass areas, all affect
the steam generator model selection.
1.
Measure length, width & height in feet of the steam/shower or tub/shower
Multiply the Length ____ x Width_____ x Height _____ =
2.
Construction Materials:
Add 5 0%
Subtract 40 %
For natural stones: natural marble,
stone, shale, glass block or concrete
For Acrylic or Fiberglass
For ceramic or porcelain tile on
Add 0%
cement board or mortar bed
3.
Ceiling Height: For each foot above 8 feet (max. of 10 feet)
Add 15%
To the Adjusted Room Volume
4. Total Adjusted Room Volume
ROOM VOLUME
Compare your Room Volume to the Chart below
and select the appropriate model.
R E S I D E N T I A L S T E A M G E N E R AT O R S S P E C I F I C AT I O N C H A R T
Amps (for Wire Total Adj. Water Usage Shipping
Model No. KW 240v/1PH)† Size‡ Room Vol. Gallons†† Dimensions* Wt. (lbs)**
MX4E 20 84 3
483-6 78
2.7 25
1
8"L x 20
3
4"H x 7
7
8"D 67
MX5E 24 100 1
679-822
3.2 25
1
8"L x 20
3
4"H x 7
7
8"D 67
MX6E 30 125 2/0
823-964
4.0 25
1
8"L x 20
3
4"H x 7
7
8"D 67
Applies to 1-8
1. Amps are for 240/1PH rated units.
2. ‡Wire size (AWG) based on minimum 90˚C rated THHN copper
conductors. Refer to the National Electrical Code for other types of
conductors.
3. *Dimensions are for generator only, without AutoFlush or plumbing
features. See page 8 for complete dimensional information.
4. **Shipping weight is for generator only, without control or steamhead.
5. †† Water usage based on 20 minutes of operation.
6. For steam rooms constructed of acrylic or synthetic materials, subtract
15% from the room volume.
7. The MrSteam Sizing Chart allows for up to 60 feet of insulated steam
piping from the generator to the steam room. If a 60 foot piping is
exceeded consult with factory.
8. Occasionally a steam room has unforeseeable or hidden construc-tion
that requires special sizing or other consideration. MrSteam is not
responsible if unconventional and/or unforeseeable materials or
construction details result in a unit that does not operate to specifi-
cation. If the sizing chart does not include the required options, please
contact MrSteam to review sizing.