Installation Guide

mr
.
steam
®
Steam@Home
®
Installation, Operation & Maintenance Manual
__________________________________________________________________________
CORRECT SIZING IS IMPORTANT
Selection of the appropriate model is impor-
tant to effectively match the heating requirements of the
steam room to the steam bath generator. Do not use a par-
ticular SAH model steam generator with a room whose “total
room volume” is less than the range shown in the SAH model
steam generator sizing chart below. Selection of a model with
a “total room volume” rating greater than the “total room
volume” may cause excessive temperature. Do not use SAH
model steam generators in a room with a “total room volume”
of less than 60 cubic feet.
2
SELECT YOUR STEAM@HOME
Materials of construction and room size affect the steam
generator model selection.
To determine the “total room volume” multiply
length x width x height of the steam room.
STEAM@HOME GENERATOR SIZING CHART
Total Room Volume* Acrylic/Fiberglass Ceramic Tile**
60 – 75 cu. ft. SAH3000 SAH3000
76 – 110 cu. ft. SAH3000 SAH4500
111 – 150 cu. ft. SAH3000 SAH6000
In considering a purchase of this steam-
bath system, please note that if you are pregnant, have a
coronary condition, are in poor health, are being treated
for any other medical condition, or are using medica-
tion or drugs, MrSteam recommends that you obtain the
approval of a physician before use. For information about
this product and safety issues, please call us at 1.800.76.
STEAM or log onto www.mrsteam.com for a copy of the
Installation, Operation & Maintenance Manual.
IMPORTANT NOTE:
SAH Model steam genera-
tors should not be used for rooms constructed of natural
stone, glass block and/or glass tile and/or for rooms hav-
ing a ceiling height in excess of 8 feet.
IMPORTANT NOTE:
The “total room volume” allows
for a maximum of 60 feet of insulated steam line from the
SAH generator to the steam room. If the 60 foot line is
exceeded refer to MrSteam MS series of residential steam
bah generators. When locating the steam generator con-
sideration of control location must be taken into account.
The maximum length for a
control cable is 60 feet. A 30 foot cable is standard.
Contact MrSteam to purchase the optional 60 ft. cable
(PN 103978-60)
Consult with supplier of acrylic and fiber-
glass enclosures for recommended steamhead
location. Use supplied Acrylic Shield PN MS-103938. See
instructions on page 7.
IMPORTANT NOTES:



NOTES:
All SAH Generators available in 240v/1PH and 208v/1PH. SAH units are not available in 3 phase. Specify voltage with order.
† Amps are for 240v/1PH rated units.
‡ Wire size (AWG) based on minimum 90˚C rated THHN copper conductors.
Refer to the National Electrical Code for other types of conductors.
See page 5 for complete dimensional information.



s
    
 
(for 240v/1PH)
Size
††
Gallons
††
  (lbs)
SAH3000 3.0 13 12
3
8 14
3
8”L x 14
7
8”H x 5
3
16”D 25
SAH4500 4.5 19 10
1
2 14
3
8”L x 14
7
8”H x 5
3
16”D 25
SAH6000 6.0 25 8
3
4 14
3
8”L x 14
7
8”H x 5
3
16”D 25
* For rooms with “total room volumes” greater than 150 cu. ft.
refer to MrSteam MS series of residential steam bath generators
** For all other room materials refer to Mr. Steam MS series
of residential steam bath generators
!