Supply Supply Return Return Downflow Furnace Installation Horizontal Left Furnace Installation Evaporator Coil Evaporator Coil Return Upflow Furnace Installation Supply CAPMP Horizontal Right Furnace Installation Supply Return A13059 A13060 Fig. 1 -- Typical Installation Multipoise Cased Coils Wide Coil Narrow Coil Field Fabricated Adapter(s) Narrow Furnace 3˝ (76mm) Wide Furnace * CAUTION: DO NOT MOUNT COIL LOWER THAN 3˝ (76mm) MINIMUM OR FURNACE FAILURE MAY RESULT A13061 Fig.
Table 1 – CAPMP Cased Coil Information SIZE (TON) FLUSH FIT TO FURNACE WIDTH CAPMP1814ALA CAPMP1917ALA CAPMP2414ALA CAPMP2417ALA CAPMP2517ALA CAPMP3014ALA CAPMP3017ALA CAPMP3614ALA CAPMP3617ALA CAPMP3717ALA CAPMP3721ALA CAPMP4221ALA CAPMP4321ALA CAPMP4821ALA CAPMP6021ALA CAPMP6024ALA CAPMP6124ALA 1.5 1.5 2.0 2.0 2.0 2.5 2.5 3.0 3.0 3.0 3.0 3.5 3.5 4.0 5.0 5.0 5.
! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in product damage. To avoid valve damage to the refrigerant control device while brazing, valves must be wrapped with a heat--sinking material such as a wet cloth. Unbend tab as shown, 4 places. A13064 Fig. 6 -- Horizontal Left Installation Self-Tapping Screws REFRIGERANT METERING DEVICE The CAPMP coil has a factory--installed hard shut--off TXV designed only for use with R--410A refrigerant.
Air Gap Above Liquid Level Condensate Line Trap Sewer Line 3” (76mm) A13067 A10216 NOTE: The unit is shipped from the factory with the horizontal drain connections capped as for vertical installations. For horizontal installations, remove the caps and place them on the vertical drain connections to keep an airtight installation.