Troubleshooting Guide
 Troubleshooting 50 
Low
pressure protection
Low
pressure protection
Are the low pressure protector 
and main control board wired 
properly
?
Are the low pressure protector 
and main control board wired 
properly
?
Method
: 
Disconnect the plug
. 
Measure the resistance of the 
low pressure protecto
r
. 
I
f the 
protector is normal the value is 
o
. 
Does a problem still exist
?
Method: Disconnect the plug. 
Measure the resistance of the 
low pressure protector. If the 
protector is normal the value is 
o. Does a problem still exist?
Yes
Yes
Replace outdoor main board
. 
Does a 
problem still exist
?
Replace outdoor main board.. 
Does a problem still exist?
No
No
Is the low pressure 
protector broken
?
Is the low pressure 
protector broken
?
Is the outdoor ambient 
temperature 
too low
?
Is the outdoor ambient 
temperature too low?
No
Yes
No
Is the
valve core of 
the 
high 
p
ressure 
valve 
fully o
pened
?
Is the
valve core of 
the 
high 
p
ressure 
valve 
fully o
pened
?
Is the indoor fan running 
properly in cooling mode
?
Is the indoor fan running 
properly in cooling mode?
No
Yes
Yes
No
Check whether the refrigerant 
system is functioning properly
.
Check whether the refrigerant 
system is functioning properly
.
When the lvel of refrigerant is not 
sufficient
, 
doe the system function 
properly after more refrigerant is added
?
When the level of refrigerant is not 
sufficient, does the system function 
properly after more refrigerant is added?
No
Reconnect the low pressure protector and main 
control board
Reconnect the low pressure protector and main 
control board
R
eplace low pressure protector
Replace low pressure protector
Open the valve core of the high 
pressure valve
Open the valve core of the high 
pressure valve
Stop the unit
Stop the unit
Please refer to the solution of
the
“
Fan 
S
p
eed 
is
operating outside of normal 
range
”
malfunction
.
Please refer to the solution of  the 
“
Fan 
Speed is operating outside of normal 
range
”
malfunction .
Note:  For  certain  models,  outdoor  PCB  could  not  be  removed  separately.  In  this  case,  the  outdoor  electric 
control box should be replaced as a whole.