Specification

Page 13
Operating Instructions
mrcool.com
Special Functions
Refrigerant Leakage Detection (optional):
When refrigerant leakage is detected, the indoor unit will display “EC” or “ELOC” code or flash LEDs,
depending on the model.
Louver Angle Memory Function (optional):
Within the scope of the safe operation angle, the horizontal louver angle is memorized and returns to
the position last selected by the user. If it exceeds the safe operation angle, it will default within the
safe operation range. However, it will not return to safe operation angle when Turbo mode is set or
the unit is in manual control or after a power interruption. Subsequently, it is strongly recommended
that the horizontal louver angle not be set too small, to avoid possible condensation leakage.
Anti-Mildew Function (optional):
When the unit is turned off, in COOL, DRY, AUTO (cool) modes, it will continue to run for about 10
minutes with a low fan airflow. This aids in drying up any condensation inside the unit to prevent
mildew growth. Do not restart the air conditioner until the unit is completely off.
Optimal Operation:
In the event of a power interruption such as a blackout, the air conditioner will stop. It will then
restart automatically and resume the previous operation when the power supply returns.
Wireless Smart Control Function:
Connect the wireless control module via the USB port in the back of the front cover of the indoor unit
for the unit to be controlled by remote control and/or smartphone app.
Clean Air Filter Reminder (optional):
After 240 hours of operation, the indoor display window will display and flash “CL” as a reminder to
CLEAN the air filter for more efficient operation. After 15 seconds, the system will revert back to the
previous display again. When the “CL” indicator appears and flashes, please press the LED button on
the remote control 4 times or press the manual control button 3 times to reset the hours. If you don’t
reset the reminder, the “CL” indicator will flash again when you restart the unit.
Replace Air Filter Reminder (optional):
After 2880 hours of operation, the indoor display window will display and flash “nF” as a reminder to
REPLACE the air filter for more efficient operation. After 15 seconds, the system will revert back to
the previous display again. When the “CL” indicator appears and flashes, please press the LED button
on the remote control 4 times or press the manual control button 3 times to reset the hours. If you
don’t reset the reminder, the “nF” indicator will flash again when you restart the unit.
Mute Function (optional):
Press the LED button on the remote to turn off the LED display and silence the buzzer of the indoor
unit to create a quiet and comfortable environment.
Operation Mode Selection
While two or more indoor units are simultaneously operating, make sure the modes do not conflict with
each other. The heat mode claims precedence over all other modes. If the unit intially started to operate
in HEAT mode, the other units can operate in HEAT mode only. For example: If the unit intially started
operating under COOL (or FAN) mode, the other units can operate under any mode except HEAT. If one
of the unit selects HEAT mode, the other operating units will stop operation and display ”--” (for units with
display window only) or the auto and operation indication light will flash rapidly, the defrost indication light
will turn off, and the timer indication light will remain on (for units without a display window).