Electrical Connections
CAUTION
Electrical work must be completed by a qualified electrical technician.
Connect the connective cables to the terminals, as identified below, with their matching
numbers on the terminal block of the indoor and outdoor units. For example, in the US models
shown in the following diagram, Terminal L1(A) of the outdoor unit must connect with terminal
1 on the indoor unit. Continue to match zone to zone for any additional connections.
See wiring diagram below and take note of the following precautions.
• Check the specifications for the power source before proceeding.
• Confirm that the electrical capacity is sufficient.
• Confirm that the cable thickness is as specified in the power source specifications.
• Always install an earth leakage circuit breaker in wet or moist areas.
• The following can be caused by a drop in voltage; vibration of a magnetic switch, damaging
the contact point, broken fuses, and disturbance of normal functioning.
• Disconnection from a power supply must be incorporated into the fixed wiring. It must have
an air gap contact separation of at least 3mm in each active (phase) conductors.
• Before accessing terminals, all supply circuits must be disconnected.
• If using magnetic rings (optional - not supplied), you must use the correct magnetic rings on
your equipment to satisfy the EMC compulsory regulations required by the international
standard CISPR 14-1:2005/A2:2011.
NOTE
This product is designed to run on 60Hz frequency which is the North American standard.
Run the main power cord through the lower line-outlet of the cord clamp. Use a magnetic ring (not
supplied, optional part) to hitch the connective cable of indoor and outdoor units after installation.
One optional magnetic ring is used for one cable.
---- This symbol indicates field wiring.
Up to Three Zones
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
Up to Four Zones
L2
L1
LPPUS REWOP Y
L1(A)
L2(A)
S(A)
L1(B)
L2(B)
S(B)
1(C) 2(C) 3(C) 1(D) 2(D) 3(D)
TO A
TO B
TO D
TO C
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
This symbol indicates optional magnetic ring.