Brochure

WWW.MRCOOL.COM
DIY® MULTI-ZONE
SPECIFICATION
MATCH UPS
DIY-MULTI3-27HP230 (27K) - 11 COMBINATIONS
9K + 9K
Two Units Three Units
12K + 12K 9K + 9K + 9K 9K + 12K + 12K*
9K + 12K 12K + 18K* 9K + 9K + 12K* 12K + 12K + 12K*
9K + 18K 18K + 18K* 9K + 9K + 18K*
DIY-MULTI4-36HP230 (36K) - 24 COMBINATIONS
12K + 24K 9K + 9K + 9K
18K + 18K 9K + 9K + 12K
9K + 18K + 18K *9K + 18K
9K + 24K
12K + 12K
12K + 18K
9K + 9K + 9K + 9K
Four Units
12K + 12K + 12K + 12K *
9K + 9K + 9K + 12K *
9K + 9K + 9K + 18K *
9K + 9K + 12K + 12K *
9K + 9K + 12K + 18K *
9K + 12K + 12K + 12K *
9K + 9K + 18K
9K + 9K + 24K *
9K + 12K + 12K
9K + 12K + 18K *
12K + 12K + 12K
12K + 12K + 18K *
12K + 12K + 24K *
12K + 18K + 18K *
Two Units Three Units
DIY-09-HP-WMAH-230B DIY-12-HP-WMAH-230B DIY-18-HP-WMAH-230B DIY-24-HP-WMAH-230B
WALL MOUNTED - Indoor Model
Power Supply
Minimum Circuit Ampacity
Max. Fuse
Net Dimensions (WxDxH)
Packaging Dimensions (WxDxH)
Net Weight
Gross Weight
Piping Size Liquidside/Gasside
V~Hz,Ph
A
A
in
in
Ibs
Ibs
in
208-230~60,1
3.0
15
31.57x7.44x11.69
37.60x17.52x14.17
19.18
37.04
1/4"-1/2"
208-230~60,1
3.0
15
31.57x7.44x11.69
37.60x17.52x14.17
19.18
37.04
1/4"-1/2"
208-230~60,1
3.0
15
42.52x8.90x13.19
49.02x19.49x15.75
30.20
54.01
1/4"-1/2"
208-230~60,1
3.0
15
42.52x8.90x13.19
49.02x19.49x15.75
31.08
54.67
3/8"-5/8"
DIY-MULTI3-27HP230 DIY-MULTI4-36HP230HEAT PUMP CONDENSER - Outdoor Model
Max Number of Zones UNIT 3 4
Power Supply
SEER
Minimum Circuit Ampacity
Max. Fuse
Net Dimensions (WxDxH)
Packaging Dimensions (WxDxH)
Net Weight
Outdoor Gross Weight
V/Hz/Ph
Btu/w
A
A
in
in
lbs
lbs
208-230/60/1
22
21
35
37.24 x 16.14 x 31.89
42.91 x 19.69 x 34.06
141.1
158.7
208-230/60/1
21.5
30
45
37.24x16.14x31.89
42.91x19.69x34.06
162
179.7
* Data provided by AHRI
Note: Size the outdoor condenser unit for the total building load. Size the
individual indoor air handler units for individual zone load.
*If all indoor units (handlers) run simultaneously, their combined
BTU output will not exceed the BTU rating of the outdoor unit
(condenser).