Installation Guide
Page 31 mrcool.com
Refrigerant Piping Connection
 NOTE
IMPORTANT
1
1
2
2
The coupling of the outdoor unit uses tapping rings, 
if you disconnect and reconnect the refrigerant
pipes, it could cause it to leak. This will also void the 
warranty.
Step 4: Connect Line Set to the Outdoor Unit
IMPORTANT:
Before you continue, it is essential that you read
the following instructions carefully. 
NOTE:
Keep excess refrigerant hose coiled. Wrap with 
protective tape and store behind the condenser in a 
horizontal position (flat with the ground).
IMPORTANT:
If you are using a 24K or greater capacity air 
handler with a 4-zone or 5-zone condenser, a line 
set adapter kit (included) needs to be installed on 
the outdoor unit before the next steps can be 
completed. Please refer to the Installation Steps 
for Line Set Adapter Kit section on the next page 
and complete before continuing.
2. Do not remove the plastic seals from the outdoor
 unit piping connectors and corresponding
 refrigerant pipes (line set to be attached) until
 immediately before you connect them.
 NOTE: Ensure the adapters attached to the
 outdoor valves have been tightened properly
 before attempting to connect the line set.
3. Align the refrigerant pipes so they line up with the
 corresponding valves and have enough slack.
 NOTE: The refrigerant pipes must be
 connected to the valves with as little stress as
 possible. Unscrew the plastic seals and place the
 screw connector of the refrigerant line just onto
 the threads of the outdoor unit, tightening the first
 few threads by hand. 
1. First remove the water
 tray on the outdoor
 unit as shown in the
 illustration to the right.
4. Using the first image below as a guide, starting with
 the bottom screw connector, you will now tighten the
 line set to the outdoor unit. Using two appropriate
 sized open-ended wrenches (depending on the
 dimensions of the connector), or adjustable crescent
 wrenches, place one of the wrenches on the nut
 marked “1”, and the other wrench on the nut marked
 “2,” Now, turn the wrench on nut “2” in the direction of
 the rotational arrow, while holding the other wrench in
 place, as seen in the first image below. Continue to
 tighten the connector until snug. NOTE: work quickly
 and make sure the screw connectors do not
 become crooked as you tighten them.
 *If an HVAC torque wrench is available: Once the
 connector is snug, using the torque wrench, tighten
 the connector to the specified torque rating, listed in
 the table on the next page (based on the
 pipe/coupling size).
 *If an HVAC torque wrench is NOT available:
 Using the two wrenches you used to tighten the
 connector, once the connector is snug, then turn the
 wrench slightly beyond that point to torque the
 connector, but do not overtighten it.
5. Repeat the same process for the top screw connector,
 using the second image below as a guide. Then, repeat
 all of these steps for every line set for all of the other
 air handlers. 
The connection ports on the outdoor condenser are labeled A,B,C,D,E, etc. The capacities of the air 
handlers you use will determine which ports they should be connected to. The largest capacity air 
handler should be connected to the “A” port. Then, the next largest capacity air handler should be 
connected to the “B” port and so on. To distinguish the connectors to be connected to the indoor units 
and outdoor unit, the refrigerant pipe connectors have been labelled “A”, “B”, “C”, “D”, and “E”. Ensure 
the marks on the connectors match the indoor units and outdoor unit respectively during connection.










