Step 3: Connect Line Set to Indoor Unit Refrigerant Pipe Connectors (both ends):
IMPORTANT:
IMPORTANT:
Before you continue, it is essential that you read 
the following instructions fully and carefully.
3.2 IMPORTANT INFORMATION
PLEASE READ FULLY BEFORE PROCEEDING TO NEXT STEP
}
.
.
.
.
.
The line sets are designed to only be installed once. 
The seal within the line set cannot be guaranteed if 
they are installed more than once. This will void the 
warranty. They also contain a compression fitting to 
seal and do not require a thread sealant (Teflon 
tape, etc.). Using a sealant may actually cause the 
connection to leak over time.
• Follow the detailed instructions for connecting the
 line set to the indoor unit and outdoor units. We can
 only provide a warranty if the line set is installed
 correctly as described in the instructions.
• To prevent leaks, ensure that the Quick Connect
®
 connectors are free of dirt. Moisture or foreign
 bodies will adversely affect the function of the
 connectors and could lead to a risk of refrigerant
 loss (not covered by the warranty).
• Only install the line set outdoors in dry weather.
• The line set must not be plastered over after being
 installed.
• Always wear work gloves and goggles and use
 caution when handling refrigerant. Please make
 sure that refrigerant is never allowed to enter the
 environment. Improper handling of refrigerant may
 be harmful to your health.
• The equipment must never be operated without the
 line set connected, otherwise the equipment will be
 damaged immediately.
• Quick Connect
®
 line set connections must only be
 tightened using the appropriate open-ended or
 crescent (adjustable-type) wrenches.
 DO NOT remove the sealing caps and stoppers
 from the line set or valves until immediately
 before they are to be connected.
 DO NOT smoke during the installation. 
3.3 Connecting the Quick Connect
®
 Line Set to 
the piping from indoor unit
1. Do not remove the plastic seals of the piping coming
 from the indoor unit, or the appropriate line set
 connector, until immediately before they are to be
 connected. The plastic seals on each of the
 connectors should be color-coded to match the 
 seals of the corresponding pipes they are to be
 connected to.
2. Align the refrigerant pipes correctly, making sure the
 dimensions of the connecting refrigerant pipe
 match. Unscrew the seals and place the screw
 connector of the line set just onto the threads of the
 piping from the indoor unit and tighten the first few
 threads by hands.
Refrigerant Piping Connection
NOTE: Depending on the capacity rating of your unit, 
(12K, 18K, 24K, 36K) the wrench sizes needed will 
vary, refer to the table below (the unit uses metric 
sizes, the standard sizes listed are approximations). 
Based on the availability of wrenches in some of the 
sizes needed, the recommended method is to use 
crescent wrenches that can be adjusted to fit the size 
each step requires.
3.1 Tools needed
 Opened-ended wrench sizes needed 
 (1x of each of these)
 12K & 18K 24K & 36K
 3/4” / 19 mm 3/4“ / 19 mm
 7/8” / 22 mm 15/16“ / 24 mm
 15/16” / 24 mm 1“ / 26 mm
 1” / 26 mm 1-1/8” / 29 mm
 1-1/4” / 31 mm
 1x HVAC Torque Wrench (if available) 
 1x Allen key, 5 mm
 1x Phillips-head screwdriver
 1x leak-detection spray or a soapy water solution 
 (liquid detergent/mix, applied by brush or spray bottle) 
 Or 2x Crescent
 (adjustable-type)
 Wrenches
If the screw connections are tightened with too little 
torque, they will leak. If they are tightened with too 
much torque, the screw connections could suffer 
damage. Please refer to the torque requirements 
section for more information. If you do not feel 
confident connecting the line set connectors yourself, 
it is imperative that you contact the MRCOOL
®
customer service team or an HVAC professional.