Installation Diagram
mrcool.com
Number of units that can be 
used together
Connected units 1-5 units
Unit: feet (meters)
When installing multiple indoor units with a single outdoor unit, ensure that the length of the 
refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements
illustrated in Fig. 4.2 below:
18K 
2-Zone
Condenser
27K
3-Zone 
Condenser
Max. combined line set 
length for all rooms
123 ft
(37.5 m)
172.2 ft
(52.5 m)
Max. line set length 
for one indoor unit
73.8 ft
(22.5 m)
73.8 ft
(22.5 m)
Max. height difference 
between indoor & outdoor unit
32.8 ft
(10 m)
32.8 ft
(10 m)
Max. height difference 
between indoor units
33 ft
(10 m)
33 ft
(10 m)
36K
4-Zone
Condenser
48K
5-Zone
Condenser
221.5 ft
(67.5 m)
73.8 ft
(22.5 m)
73.8 ft
(22.5 m)
221.5 ft
(67.5 m)
32.8 ft
(10 m)
49.2 ft
(15 m)
33 ft
(10 m)
33 ft
(10 m)
Line Set Length Specifications 
33 ft (10 m)
Indoor unit 
Indoor unit 
Indoor unit Outdoor unit 
18K-36K 
Condenser
32.81 ft (10 m)
48K 
Condenser
49.21 ft (15 m)
18K-36K 
Condenser
32.81 ft (10 m)
48K 
Condenser
49.21 ft (15 m)
Maximum Height
Difference
Fig. 4.2