Troubleshooting Guide
 Troubleshooting 15 
For key board models,
Number of 
Presses
Display Remark
0  Normal display Displays running frequency, running state, or malfunction code 
1
Quantity of indoor units with 
working connection
Display Number of indoor unit
 1 1
 2 2
 3 3
 4 4
2
Outdoor unit running mode 
code
Stanby: 0,Fan only: 1, Cooling: 2, Heating: 3, Forced cooling: 
4, Forced defrostling: A
3 Indoor unit A capacity
The capacity unit is horse power. If the indoor unit is not 
connected, the digital display shows the following: “--”
(9K:1HP,12K:1.2HP,18K:1.5HP) 
4 Indoor unit B capacity
5 Indoor unit C capacity
6 Indoor unit D capacity
7 Indoor unit E capacity
8
Indoor unit A capacity demand 
code
Norm code*HP
(9K: 1HP,12K: 1.2HP,18K: 1.5HP)
9
Indoor unit B capacity demand 
code
10
Indoor unit C capacity demand 
code
11
Indoor unit D capacity demand 
code
12
Indoor unit E capacity demand 
code
13
Outdoor unit amendatory 
capacity demand code
14
The frequency corresponding 
to the total indoor units' 
amendatory capacity demand
15
The frequency after the 
frequency limit
16
The frequency sending to 
compressor control chip
17
Indoor unit A evaporator outlet 
temperature (T2BA)
If the temperature is lower than -9°C, the digital display 
shows “-9.” If the temperature is higher than 70°C, the digital 
display shows “70.” If the indoor unit is not connected, the 
digital display shows: “--”
18
Indoor unit B evaporator outlet 
temperature (T2BB)
19
Indoor unit C evaporator outlet 
temperature (T2BC)
20
Indoor unit D evaporator outlet 
temperature (T2BD)
21
Indoor unit E evaporator outlet 
temperature (T2BE)