Troubleshooting Guide
 Troubleshooting 29 
Indoor / outdoor units communication error
Start: Power off , then Power on the 
A/C by the Breaker reconnect the 
power wire). Is it still displaying the 
error code ?
Yes
No
Replace  outdoor  main  PCB 
assembly (include wiring) totally
Check wiring on the outdoor and 
indoor terminal follow the wiring 
diagram. Is all connecting correctly?
Yes
No
Measure Volts, is it moving 
alternately between positive 
value and negative value? (Volts is 
the voltage between S and N).
Turn on all indoor units by remote 
controller. Is all indoor unit 
display the same?
Turn off the all indoor units
. 
Is IPM 
power, LED, or operating
LED 
lamp 
On?
Yes
A: Is all the wiring 
between terminal and 
Indoor PCB connect ok?
No
Yes
A
No
Reconnect the wiring
Is indoor units number correct? 
Check on the outdoor check point  (2 for 
dual zone, 3 for 3-zone, 4 for 4-zone, 
5 for 5-zone).
Yes
No first time
Yes
Yes
Replace   the Indoor PCB
Power on by remote 
controller, I
Is it still 
displaying the error code
after 3 minutes?
Problem is solved
No second time
No
Yes
Reconnect the wiring
No
Replace IPM board or the 
outdoor main PCB
No
Is the reactor connecting 
well
No Reconnect the wiring
Replace the outdoor main 
PCB
Yes
No
Is main board“ ” 
lamp on? . 










