Troubleshooting Guide
 Troubleshooting 35 
Current protection of compressor 
Was the protection activated 
in standby?
Yes
Yes
Is the current normal
Yes
No
Replace the outdoor main PCB
Is the power voltage is 
normal?
Is outdoor terminal voltage 
normal
Restart the unit when the power 
supply returns to normal
No
Yes
No
Reconnect the 
power wiring
Yes
Is the voltage between L and 
N is normal
Yes
Is the input voltage of the 
bridge rectifier is normal
No
No
 Is the power wiring 
wired correctly?
Reconnect L and N
Are L and N wired 
properly?
Reconnect the 
bridge rectifier 
 Is the bridge 
rectifier wired 
properly?
No
No
Yes
Replace the PFC module (if this has not 
been done already)
No
Is the voltage between P and 
N normal refer according to 
Appendix
Replace the bridge 
rectifier
No
Is the bridge rectifier 
functioning normally?
Is the wiring of the 
reactor or inductance 
properly wired?
Reconnect the 
wiring 
No
Are the reactor and 
inductance functioning 
normally
Yes
Replace reactor or 
inductance
No
 Is the outdoor ambient 
temperature is higher than 
50
?
No
Stop the unit 
Yes
Is the outdoor unit 
ventilation functioning 
properly?
Yes
Ensure that the outdoor unit 
ventilate is working properly
 Is the heat exchanger dirty?
No
Clean the heat exchangerYes
Check whether the refrigerant 
system is running normally
 Replace outdoor main 
board. Does a problem still 
exist?
No
No
Is the outdoor fan running 
properly?
Refer to the solution to the 
malfunction of fan speed being out 
of control. Find the cause and 
resolve the issue
No
Yes
No
Yes
Yes
Is system pressure too high?
Recycle the overcharged 
refrigerant
Yes










