8.6  PC 00 (IPM malfunction diagnosis and solution) & (IDU) PC 04 (Inverter compressor drive 
error diagnosis and solution)
Description: PC 00/(ODU)P6:When the voltage signal the IPM sends to the compressor drive chip is abnormal, the LED 
displays the failure code and the AC turns off.
(IDU)PC 04:The driven chip cannot detect the right rotor position of compressor
Recommended parts to prepare:
•   Connection wires
•   IPM module board
•   Outdoor fan assembly
•   Compressor
•   Outdoor PCB
•   Reactor or inductance
•   Bridge rectifier
Troubleshooting and repair:
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the 
IPM is defective. Otherwise, please follow the procedure below: