Troubleshooting Guide
 Troubleshooting 37 
IPM module protection
IPM module protection
Yes
Is the power voltage normal
?
Is the power voltage normal
?
Is the
o
utdoor terminal voltage
normal
Is the
o
utdoor terminal voltage
normal
Restart the unit when the power supply 
returns to normal
Restart the unit when the power supply 
returns to normal
No
Yes
No
Reconnect
the 
power wires
Reconnect  the 
power wires
Yes
Is 
the voltage between
L
and N
normal
Is  the voltage between  L  and N 
normal
Yes
Is the
input voltage of 
bridge 
rectifier
normal
Is the input voltage of bridge 
rectifier normal
No
No
Are the power wires 
connected properly
?
 Are the power wires 
connected properly?
Rec
onnect
L and N
Rec
onnect
L and N
Are L and N wired 
correctly
?
Are L and N wired 
correctly?
Reconnect
the 
bridge rectifier
Reconnect
the 
bridge rectifier
Is the bridge rectifier 
properly wired
?
Is the bridge rectifier 
properly wired?
No
No
Yes
Replace the PF
C module
(
If 
This 
has
not 
been done already
)
Replace the PFC module (If this has  not 
been done already)
No
Is 
the voltage between
P
and N
properly
wired
according to
9
.
Check Procedures
Is 
the voltage between
P
and N
properly
wired
according to
9
.
Check Procedures
Replace the 
bridge rectifier
Replace the bridge rectifier
No
Is the
bridge rectifier
operating
normally
?
Is the
bridge rectifier
operating
normally
?
Are the
r
eactor 
or 
Inductance wired 
properly
?
Are the
r
eactor 
or 
Inductance wired 
properly
?
Re
connect 
the wiring 
Reconnect the wiring 
No
Are the 
r
eactor 
or 
inductance
normal
?
Are the  reactor or 
inductance  normal?
Yes
Replace r
eactor 
or 
inductance
Replace reactor or 
inductance
No
Is the connecting 
wire
between the main board and 
the IPM 
board
connected 
tightly
?
Is the connecting 
wire
between the main board and 
the IPM 
board
connected 
tightly
?
Rec
onnect
the main board 
and IPM board
Reconnect  the main board 
and IPM board
No
Is the outdoor unit 
ventilation in working order
?
Is the outdoor unit 
ventilation in working order?
Yes
Make sure
that the outdoor unit is 
ventilating properly
Make sure
that the outdoor unit is 
ventilating properly
Check whether the refrigerant system is 
in working order
Check whether the refrigerant system is 
in working order
No
Is the outdoor fan running 
properly
?
Is the outdoor fan running 
properly
?
Refer to the solution for 
themalfunction of the fan speed 
being out of control 
. 
Find the cause 
and resolve the problem
Refer to the solution for 
the malfunction of the fan speed 
being out of control . Find the cause 
and resolve the problem
No
Yes
No
Yes
Yes
Is 
the compress is
running
normally
?
Is the compressor 
running normally?
Yes
Replace the compressor
Replace the compressor
No
Replace 
IPM
Board
. 
Is the problem 
resolved
?
Replace 
IPM
Board
. 
Is the problem 
resolved
?
Replace 
the 
outdoor main 
PCB
. 
Is 
the problem resolved
?
 Replace the outdoor main PCB. Is 
the problem resolved?
No
Is the connecting 
wire
of the 
compressor is connected 
correctly or tightly
Is the connecting 
wire
of the 
compressor is connected 
correctly or tightly
Rec
onnect
he connecting 
wire of the compressor
Reconnect  the connecting 
wire of the compressor
No
Yes
Yes
Note:  For  certain  models,  outdoor  PCB  could  not  be  removed  separately.  In  this  case,  the  outdoor  electric 
control box should be replaced as a whole.










