7.7  EL 0C (Refrigerant Leakage Detection diagnosis and solution)
Description: Define the evaporator coil temperature T2 of the compressor just starts running as Tcool. 
In the beginning 5 minutes after the compressor starts up, if T2< Tcool-1°C(1.8°F) does not keep continuous 4 seconds 
and compressor running frequency higher than 50Hz does not keep for 3 minutes, and this situation happens 3 times, 
the LED displays the failure code and AC turns off.
Recommended parts to prepare:
•   T2 sensor
•   Indoor PCB
•   Additional refrigerant
Troubleshooting and repair:
Power off, then restart the unit 2 minutes later.
Are any leakages 
present?
Check System for blockages  and 
clear  blockages if present.
Does a problem remain?
Put your hands in front of the 
indoor air outlet.
YES
Is there cool 
air blowing out from 
indoor air outlet?
Is it securely 
attached?
Replace  the 
indoor PCB
YES
Check the T2 sensor.
YES
Check system  for leakages.
NO
NO
Repair the leakage and 
recharge the refrigerant.
YES
NO