Troubleshooting Guide

Table Of Contents
MRCOOL Universal Service Manual
10
detected open for continuously a little time. Under discharge high temperature protection, system will be shut
down and display error code E4. When discharge high temperature protection occurs, system will restore
operation if the discharge high temperature sensor is detected to be reclosed within a few minutes after shutdown.
If discharge high temperature protection occurs for several times in a period of time, system will not restore
operation automatically. You need to manually turn off the unit before restarting up the unit.
2.3 Functions
2.3.1 Set Capacity Dial Code
Set the capacity of the outdoor unit through the four-digit dial codes of the outdoor unit main control board.
Specific dialing definition, the first digit dial code distinguishes the capacity.
Capacity
24K
36K
48K
60K
Dial Codes
2.3.2 Set Defrost Mode
The second digit dial code are selecting the defrost mode. The following table shows the 36K outdoor unit
dial code for example. Mode 1 is conventional defrostmode 2 is suitable for defrosting in ultra-low temperature
environment.
Defrost mode
Outdoor unit dial code
Defrost mode 1
(Default)
Defrost mode 2
2.3.3 Set Operating Mode
The third digit dial code and the fourth digit dial code are selecting the operating mode. The following table
shows the 36K outdoor unit dial code for example. Standard mode is the conventional mode.