3.4.3 “E4” Compressor Air Discharge High-temperature Protection
Error display: ODU mainboard LED displayer
Error judgment condition and method:
Test the compressor discharge temperature through compressor discharge pipe and shell top temperature
sensor. If the tested temperature value is higher than 115, the unit will stop for protection
Possible reason
■Cut-off valve of ODU is not fully opened;
■Electronic expansion valve is abnormal;
■Outdoor or indoor fan is not working properly;
■IDU filter or air duct is blocked (cooling mode);
■Ambient temperature exceeds allowable operation range;
■Refrigerant charging amount is insufficient;
■System pipeline is blocked;